Wiring
3.2.2 Current Output (0 to +20 and +4 to +20 mA)
Internal circuit diagram and connection diagram
Terminal layout
NOTES
•
Use double-core twisted-pair shielded wires for analog output signals.
•
Ground the shielding of the shielded wire on the load equipment side.
However, depending on the conditions of the external noise, it may be
better to ground the shielding externally or not to ground the shielding.
•
Do not place the analog output wiring close to AC lines, high-tension lines,
or load lines other than PLC wires or bundle the analog output and other
wires together.
•
The NC terminals of the analog output terminal block are unused. Do not
use these terminals to relay wires because the terminals include those
connected internally.
3-4