4–20mA Connections
The following table provides a function summary of each terminal if the detector is ordered in 4-20mA mode.
Terminal
Terminal No.
+24v
1
0v
2
A
3
B
4
VID+
5
VID-
6
485A
7
+24v
8
0v
9
C
10
D
11
ALRM
12
ALRM
13
485B
14
If the detector is connected in the above manner if a fi re alarm is signalled then the 4-20mA outputs generate 18mA
if a fault develops the 4-20mA signal indicates 0 or 2 mA dependant on the fault see table for default current levels. If
terminals 3 & 4 are disconnected from their connections these wires then provide a RS485 connection to the detector.
This connection may then be used to up load or down load information to the detector.

Default 4-20mA settings

Event
Output
Catastrophic Failure
Optical Fault
Healthy condition
Alarm
Over range
There is a tolerance on the mA outputs of ±5%, other values maybe selected at the point of order.
Description
+24V Supply A
0V Supply A
Tie to +24 Volts at panel
4-20 mA source
Video +Ve
Video –Ve
RS485 termination +Ve
+24V Supply B optional
0V Supply B optional
Not used
Do not connect
Do not connect
Not used
RS485 termination -Ve
0mA
2mA
4mA
18mA
21mA
Installation of the Dräger Flame Detector 5000
1
7
8
14
6
5
4
2
1
VIDEO -VE
VIDEO +VE
4-20mA Source
0 VDC
+24 VDC
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents