Detector Wiring Terminals (Rear Detector With Cover Removed); Relay Mode Connections - Dräger Flame 5000 Technical Manual

Colour cctv flame detector
Hide thumbs Also See for Flame 5000:
Table of Contents

Advertisement

Installation of the Dräger Flame Detector 5000

Detector Wiring Terminals (Rear Detector with cover removed)

Relay Mode Connections

The following table provides a function summary of each terminal if the detector is ordered in relay mode.
Terminal
Terminal No.
+24v
1
0v
2
A
3
B
4
VID+
5
VID-
6
485A
7
+24v
8
0v
9
C
10
D
11
ALRM
12
ALRM
13
485B
14
If the detector is connected in the above manner and if a fi re alarm is signalled, with the alarm resistor connected
between terminals 12 & 13, then the alarm resistor will appear across terminals 3 & 4. The EOL resistor connected
between terminals 10 & 11 normally appears across terminals 3 & 4 and in the event of a fault the resistor appears open
circuit. If terminals 3 & 4 are disconnected from the fi re panel, these wires then provide a RS485 connection to the
detector. This connection may then be used to up load or down load information to the detector.
14
1
8
Description
+24V Supply A
0V Supply A
Sense from fi re panel
Return signal to fi re panel
Video +Ve
Video –Ve
RS485 termination +Ve
+24V Supply B
0V Supply B
EOL resistor
EOL resistor
Alarm Resistor
Alarm Resistor
RS485 termination -Ve
7
14
1
7
8
14
6
5
4
3
2
1
VIDEO -VE
VIDEO +VE
To Fire Panel
From Fire Panel
0 VDC
+24 VDC