Two-Speed Motor - Emerson Digistart IS1x0043B series User Manual

Digistart is series soft starters for 3 phase induction motors
Table of Contents

Advertisement

Safety
Rating
Mechanical
Information
Data
Installation

10.7 Two-speed motor

The Digistart IS can be configured for control of dual speed Dahlander type motors, using a high speed contactor (KM1), low speed
contactor (KM2) and a star contactor (KM3).
Pole Amplitude Modulated (PAM) motors alter the speed by effectively changing the stator frequency using external
NOTE
winding configuration. Soft starters are not suitable for use with this type of two-speed motor.
When the soft starter receives a high speed start signal, it closes the high speed contactor (KM1) and star contactor (KM3), then
controls the motor according to the primary motor settings.
When the soft starter receives a low speed start signal, it closes the low speed contactor (KM2). This closes Input A and the
Digistart IS controls the motor according to the secondary motor settings.
Figure 10-7 Two-speed motor
Contactors KM2 and KM3 must be mechanically interlocked.
NOTE
Parameter settings:
Pr 3A Input A Function (terminals DI4, +24V)
Select 'Motor Set Select' - assigns Input A for Motor set selection.
Set high speed performance characteristics using the primary motor settings.
Set low speed performance characteristics using the secondary motor settings.
Pr 4G Relay C Action
Select 'Trip' - assigns Trip function to Relay Output C
If the Digistart IS trips on supply frequency (Pr 16H Frequency) when the high-speed start signal (9) is removed, modify
NOTE
the frequency protection settings.
80
Electrical
Keypad
Quick Start
Installation
and
Commissioning
Status
www.controltechniques.com
Operation Programming Diagnostics
1
2
3
4
5
6
7
8
9
F1
KA1
KA2
KM1
KM2
KM3
S1
COM4, RLC4,
RLO4
Application
Technical
Maintenance Options
Examples
Data
Control voltage
Remote control inputs
Motor thermistor input
RTD/PT100 input
Relay outputs
Three-phase supply
Motor terminals
Remote low speed start input
Remote high speed start input
Semiconductor fuses (optional)
Remote start relay (low speed)
Remote start relay (high speed)
Line contactor (high speed)
Line contactor (low speed)
Star contactor (high speed)
Reset contact
Relay output C
Digistart IS User Guide
Issue: 4

Advertisement

Table of Contents
loading

Table of Contents