Setup procedure

Table 6-1 Basic setup procedure
Action
Before power-up
Ensure:
Power up the starter
Ensure:
Program parameters
The Quick Setup Menu makes it easy to configure the Digistart IS for common applications. The Digistart
IS selects the parameters relevant to the application and suggests a typical setting, and you can adjust
each parameter to suit your exact requirements.
Press the M button.
To validate the Quick Setup Menu, press M again.
Select the application of your choice from the list.
The following applications are available through the Quick Setup Menu:
Use the M button to select the characteristics you want to modify and adjust the value using
To confirm the selection, press the M key.
To exit the Quick Setup Menu and go back to the standard display, press
For more information on the Quick Setup Menu, see Quick setup details.
For applications not covered by the Quick Setup Menu, select the Standard Menu, then Menu 1 - Primary
Motor Set and Menu 2 - Start/Stop Modes-1.
Press M to enter in the required menu.
The following parameters should be set to suit the requirements of the application:
For parameter details, see Parameter descriptions on page 51.
Start the motor
Ensure:
To start the motor, close terminal DI1, +24V.
To stop the motor, open terminal DI2, +24V (or DI4, +24V if an emergency stop is required).
36
Electrical
Keypad
Quick Start
Installation
and
Commissioning
Status
The starter is not receiving a start signal
The motor is connected to the starter
The motor connection is correct
The correct supply voltage is available
The Ready LED activates
Pump (centrifugal, submersible)
Fan (damped, undamped)
Compressor (screw, reciprocating)
Conveyor
Crusher (rotary, jaw)
1A Motor Full Load Current
2A Start Mode
2B Current Limit
2D Start Ramp Time
2I Stop Time
2H Stop Mode (if required)
The status screen is shown on the starter display
The following terminals are closed: DI4, +24V, DI2, +24V and DI3, +24V