Send Command (When Mewtocol-Com Is Used) - Panasonic FP7 User Manual

Cpu unit. com port communication
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

5.4.2 SEND Command (When MEWTOCOL-COM is Used)

 Command format
Setting
Settings
items
i
Specify the operation unit.
S
Specify the header of the source node data area. (Note 1)
n
Specify the No. of sent data.
D1
Specify the partner station no. (Note 2) (Note 3)
Specify the initial address of the receiver node data area in the partner
D2
node. (Note 4)
Specify the device area in the source node to save the execution result
D3
code (one word).
(Note 1) Transmission methods vary by the type of device to be specified for the operands [S] and [D2].
16 bit device: WX, WY, WR, WL, DT, LD
1 bit device: X, Y, R, L, DT, n, LD, n
(Note 2) The No. of sent data is on a word basis for register transmission, and on a bit basis for bit transmission.
(Note 3) When "0" is specified for partner station no., global transmission is applied. In this case, no response
message is received from the partner side.
(Note 4) Bit device DT, n and LD, n cannot be specified for the header of the receiver data in the partner node.
(Note 5): Device that can be specified for [D3] are: WX, WY, WR, WL, DT, LD. Saved as one word in the specified area.
0: Normal completion
1: Communication port is being used for master communication
2: Communication port is being used for slave communication
3: No. of master communication commands that can be used simultaneously has been exceeded
4: Sending timeout
5: Response reception timeout
6: Received data error
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5.4 MEWTOCOL-COM Master Communication (SEND)
Device to be specified for [S2] and [D1]
Setting range
US / SS
-
1 - 507 words
or 1 bit
0 - 99
0 - 99999
(Note 5)
Transmission
method
Register
transmission
Bit transmission
5-9