Panasonic FP7 User Manual page 34

Cpu unit. com port communication
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

Wiring the COM. Port
 Terminal layout (in the setting of RS-422)
Terminal
LED part
no.
Symbol
1
CH1
SD
2
RD
3
485
4
422
5
-
6
CH2
SD
7
RD
8
485
9
422
(Note 1) Do not connect anything to Terminal No.5.
(Note 2) Route between CH1 and CH2 are insulated inside.
 Example of wiring (in the setting of RS-422)
AFP7CCM2
Terminal
Terminal
No.
part symbol
1
+ / S
Sent Data 1 (+)
2
- / S
Sent Data 1 (-)
3
+ / R
Received Data 1 (+)
4
- / R
Received Data 1 (-)
5
6
+ / S
Sent Data 2 (+)
7
- / S
Sent Data 2 (-)
8
+ / R
Received Data 2 (+)
9
- / R
Received Data 2 (-)
2-18
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Terminal
Functions that
part
can be allocated
Symbol
+ / S
Sent Data (+)
- / S
Sent Data (-)
+ / R
Received Data (+)
- / R
Received Data (-)
-
-
+ / S
Sent Data (+)
- / S
Sent Data (-)
+ / R
Received Data (+)
- / R
Received Data (-)
Signal name
Functions
SD (+)
SD (-)
RD (+)
RD (-)
SD (+)
SD (-)
RD (+)
RD (-)
Signal direction
PLC → External device
PLC → External device
PLC ← External device
PLC ← External device
-
PLC → External device
PLC → External device
PLC ← External device
PLC ← External device
Terminal
RD (+)
RD (-)
SD (+)
SD (-)
Terminal
RD (+)
RD (-)
SD (+)
SD (-)
Ports that can be
allocated
in the software
COM.1
-
COM.2
Partner 1
Signal name
Received Data (+)
Received Data (-)
Sent Data (+)
Sent Data (-)
Partner 2
Signal name
Received Data (+)
Received Data (-)
Sent Data (+)
Sent Data (-)

Advertisement