7.4 MEWTOCOL-COM Master Communication (SEND)

7.4.1 Write Data into an External Device

Instructions
In master communication, PLC has the sending right, and executes communication by sending
commands to devices that support MEWTOCOL, and receiving responses. Messages in
accordance with the protocol are automatically generated by PLC. In the user program, reading
and writing can be done simply by specifying the station no. and memory address and
executing SEND/RECV instructions.
PLC
DT100
100
DT101
0
・・・・・・
・・・・・・・・
・・・・・・
・・・・・・・・
Sample program
● Send commands from the COM.1 port of the CPU unit, and write the content of PLC's data
register DT100 to DT101 into the data area of an external device (station no. 1) DT400 to
DT401.
● Confirm that the unit is in the master mode (XC), and that the sending process is not in
progress for the same port (YC), and start up the SEND instruction.
● In the UNITSEL instruction, specify the slot No. (U0) and the COM. port No. (U1).
● In the SEND instruction, specify and execute the sender initial address (DT100), No. of data
(U2), "Transmit to" station no. (U1), and initial address (DT400).
(Note 1)
The unit number and COM. port number in the above program is applied when the COM.1 port of the
CPU unit is used.
WUME-FP7COM-07

7.4 MEWTOCOL-COM Master Communication (SEND)

Command messages
%01#WDD004000040164000000 (BCC) C
%01$WD (BCC) C
Response messages
Perform writing by specifying Unit number and
address using the SEND instruction
External devices that
support MEWTOCOL-COM
R
DT00400 100
DT00401 0
・・・・・・
R
・・・・・・
・・・・・・・・
・・・・・・・・
7-15