Technical Data; Ac Drive Power Ratings; Mains Voltage 208-240 V - Vacon 100 Installation Manual

Hide thumbs Also See for 100:
Table of Contents

Advertisement

vacon • 71
7.
T
ECHNICAL DATA
7.1

AC drive power ratings

7.1.1

Mains voltage 208-240 V

Mains voltage 208-240V, 50-60 Hz, 3~
Converter
type
0003
0004
0006
0008
0011
0012
0018
0024
0031
0048
0062
0075
0088
0105
0140
0170
0205
0261
0310
*
See chapter 7.1.3.
Table 29. Power ratings of Vacon 100, supply voltage 208-240V.
NOTE: The rated currents in given ambient temperatures (in Table 31) are achieved only when
the switching frequency is equal to or less than the factory default.
7
Loadability
*
Low
Rated continuous
Input
current I L
current I in
[A]
[A]
3.7
3.2
4.8
4.2
6.6
6.0
8.0
7.2
11.0
9.7
12.5
10.9
18.0
16.1
24.2
21.7
31.0
27.7
48.0
43.8
62.0
57.0
75.0
69.0
88.0
82.1
105.0
99.0
143.0
135.1
170.0
162.0
208.0
200.0
261.0
253.0
310.0
301.0
Motor shaft power
230 supply
10% overload
10% overload
current
40°C
[A]
[kW]
4.1
0.55
5.3
0.75
7.3
1.1
8.8
1.5
12.1
2.2
13.8
3.0
19.8
4.0
26.4
5.5
34.1
7.5
52.8
11.0
68.2
15.0
82.5
18.5
96.8
22.0
115.5
30.0
154.0
37.0
187.0
45.0
225.5
55.0
287.1
75.0
341.0
90.0
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205

Technical data

208-240V
supply
10% overload
40°C
[hp]
0.75
1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
125.0

Advertisement