Technical data
7.2

Vacon 100 - technical data

Mains connection
Motor connection
Control characteris-
tics
Ambient conditions
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Input voltage U
in
Input frequency
Connection to mains
Starting delay
Output voltage
Continuous output
current
Output frequency
Frequency resolution
Switching frequency
(see parameter
P3.1.2.1)
Frequency reference
Analogue input
Panel reference
Field weakening point 8...320 Hz
Acceleration time
Deceleration time
Ambient operating
temperature
Storage temperature
Relative humidity
Air quality:
• chemical vapours
• mechanical particles
Altitude
208...240V; 380...480V; -10%...+10%
50...60 Hz -5...+10%
Once per minute or less
4 s (MR4 to MR6); 6 s (MR7 to MR9)
0-U
in
I
:Ambient temperature max. +40°C, up to
L
+50°C with derating; overload 1.1 x I
min./10 min.)
0...320 Hz (standard)
0.01 Hz
1.5...10 kHz;
Defaults:
MR4-6: 6 kHz (except 0012 2, 0031 2, 0062 2,
0012 4, 0031 4 and 0061 4: 4 kHz)
MR7: 4 kHz
MR8-9: 3 kHz
Automatic switching frequency derating in
case of overload.
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
0.1...3000 sec
0.1...3000 sec
I
: -10°C (no frost)...+40°C; up to +50°C with
L
derating
-40°C...+70°C
0...95% R
, non-condensing, non-corrosive
H
Tested according to IEC 60068-2-60 Test Ke:
Flowing mixed gas corrosion test, Method 1
(H
S [hydrogen sulfide] and SO
2
dioxide])
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1,000m
1-% derating for each 100m above 1,000m
Max. altitudes:
208...240V: 4,500m (TN and IT systems)
380...480V: 4,500m (TN and IT systems)
Voltage for I/O signals:
Up to 2,000m : Allowed up to 240V
2,000m...4,500m: Allowed up to 120V
Corner-grounding: up to 2,000m only.
vacon • 74
(1
L
[sulfur
2
7