Warning Words, Extended Status Word
and Alarm Word
Warning Word, Extended Status Word and Alarm Word are shown in
hex format on the display. If there is more than one warning or alarm,
the sum of the warnings or alarms will be shown.
The descriptions of the Extended Status Words, Warning Words and
Alarm Words can be read out via the serial bus in parameter 531,
Warning Word; 532, Extended Status Word; and 529, Alarm Word.
Hex Code
Extended Status Word
00000001
Overvoltage control active
00000002
Start delay
00000004
Sleep boost active
00000008
Sleep mode active
00000010
Automatic motor adaptation completed
00000020
Automatic motor adaptation running
00000040
Reversing and start
00000080
Ramp operation
00000100
Reversing
00000200
Speed = reference
00000400
Running
00000800
Local reference = 1
Remote controlled reference = 0
00001000
OFF mode = 1
00002000
Auto mode = 0, Hand mode = 1
00004000
Start blocked
00008000
Start blocked signal missing
00010000
Freeze output
00020000
Freeze output blocked
00040000
Jogging
00080000
Jog blocked
00100000
Stand by
00200000
Stop
00400000
DC stop
00800000
Drive ready
01000000
Relay 123 active
02000000
Drive ready
04000000
Control ready
08000000
Start prevented
10000000
Profibus OFF3 active
20000000
Profibus OFF2 active
40000000
Profibus OFF1 active
80000000
Reserved