General Information - WebDoor CADET PRO Installation And Instruction Manual

Non-handed low energy swing door opener
Table of Contents

Advertisement

General
1. All wiring must conform to standard wiring practice in accordance with national and local wiring codes.
2. Door must swing freely through the entire opening and closing cycle before beginning the installation. Typically, doors are hung on
hinges [5" (127mm) max. width] or 3/4" (19mm) offset pivots.
3. An incorrectly installed or improperly adjusted door opener can cause property damage or personal injury. These instructions should
be followed to avoid the possibility of misapplication or maladjustment.
Note: Unless otherwise noted, all dimensions are given in inches (millimeters).
General Templating Information
Before beginning the installation, verify that the door frame is properly reinforced and is well anchored in the wall.
Concealed electrical conduit and concealed switch or sensor wires should be pulled to the frame before proceeding.
Suggested Fasteners for Frame
 #14 x 2-3/4" (70mm) long sheet metal screws for wood.
Suggested Fasteners for Door
 #12, #14, Wood screws, Sheet Metal screws, Self-tapping screws of varying lengths depending on applications.
Note: The fastener components listed above are merely suggestions. A technician should use their best discretion to determine what
components they'll need to complete the job.
Safety Sensors
The control board can accommodate overhead and door mounted safety sensors. To permit safe passage through, the closing door will
reverse (if equipped with door mounted safety sensor) to the fully open position if an obstruction is encountered during the closing phase.
If equipped with door monitor sensor, the opener will then resume its standard closing cycle and repeat if the obstruction remains.
If equipped, the safety sensor on the closing side of the door will activate while the door is closing, the door will reverse to open.
If equipped, the safety sensor on the opening side of the door is activated by another pedestrian while the door is opening, the door
will stall until that pedestrian has left the opening area.
If the door is equipped with an overhead safety sensor, the door will not open if there is an obstruction or pedestrian in the swing
path.
If the door is equipped with an overhead presence sensor and in the closed position, the door will not open if there is an obstruction
or pedestrian in the swing path.
Activation Devices
The CADET PRO Opener is compatible with all devices using a dry contact switch, usually hardwired or radio controlled. All activation
signals should be wired to Activation 1 and Common. When a door is used in a vestibule the built-in sequence can be used to allow both
doors to operate in sequence. This is achieved by wiring Activation 2 on both boards together. The delay at which the second door
opens after the first door opens is set using function #5 on the programming schedule, up to 5 sec delay is achievable.
Push Plate or Knowing Act Device
Test the Knowing Act Device. The door should swing smoothly to the open position and stop without impact. After a time delay
(normally 1s to 5s) the door should close smoothly.
Repeat on the other side of the opening if the door has two-way operation.
Electric Strike
This opener control board is capable of supplying power (24VDC, 6W or 250mA) to the electric strike. When the door is triggered a
contact closure occurs across Ground and N.O. or N.C. to energize the strike. The strike has a delay function from 0.125 seconds - 2
seconds.
NOTE: If there is more than one push plate or Knowing Act Device on each side of the door, each should be tested.
WARNING: Make sure 120VAC (60Hz) input power is turned off at facility's main circuit breaker before proceeding with installation.

1.0 GENERAL INFORMATION

Page 3 of 31
WebDoor
info@webdoor.com
www.webdoor.com
Issued Date: 2017-03-28