FireClass FC501-HK Installation Manual page 86

Fc501 series addressable fire control panels
Hide thumbs Also See for FC501-HK:
Table of Contents

Advertisement

TERM.
+L1-
LEFT
+L1-
RIGHT
+L2-
LEFT
+L2-
RIGHT
+L3-
LEFT
+L3-
RIGHT
SH
+RS485-
SERIAL BUS. Terminals to connect the FC500REP and FC500MFI modules
[M]
[24R]
[M]
[24A]
[LE]
[LI]
[-]
[NC]
[NO]
[C]
in the event of ALARM è [C] connected to [NO] with [NC] open
FIRE
[NC]
[NO]
[C]
FAULT
+BAT-
Programmable Outputs(Open collector)- Silenceable-Bypassable
[OC1]...
[OC2]
[MIK]
[SPK]
[BLK]
[RED]
(Programmable, SC2 only),Supervised, Silenceable, Bypassable (Disabled) ALARM Outputs:
[SC1]
Panel in Standby è negative on [+] terminal; positive 27.6V on [–] terminal
[SC2]
Panel in Alarm è positive 27.6V on [+] terminal; negative 0 V on [–] terminal
Table 13 Terminals description.
86
DESCRIPTION
(+)Loop 1-Positive signal, left side.
(-)Loop 1-Negative signal (return), left side
(+)Loop 1-Positive signal, right side.
(-)Loop 1-Negative signal (return), right side
(+)Loop 2-Positive signal, left side.
(-)Loop 2-Negative signal (return), left side.
(+)Loop 2-Positive signal, right side.
(-)Loop 2-Negative signal (return), right side.
(+)Loop 3-Positive signal, left side.
(-)Loop 3-Negative signal (return), left side.
(+)Loop 3-Positive signal, right side.
(-)Loop 3-Negative signal (return), right side.
Terminal for connection of the shield of cables
24 V RESET ABLE AUXILIARY POWER
negative present on terminal [M];
positive present on terminal [24R].
24 V AUXILIARY POWER SUPPLY:
negative present on terminal [M];
positive present on terminal [24A].
Terminal for connection of the external telephone line
Terminal for connection of the internal telephone line
Terminal for connection of the Earth cable
FIRE ALARM OUTPUT - Non-Supervised:
standby è [C] connected to [NC] with [NO] open
FAULT ALARM OUTPUT - Non-Supervised:
standby è [C] connected to [NC] with [NO] open
in the event of fault è [C] connected to [NO] with [NC] open
BATTERY CONTROL PANEL POWER SUPPLY
(Disabled)-Supervised
(The polarity is not programmable)
FUTURE USE
Addressable Fire Panel
MAIN BOARDS
SUPPLY:
v(V)
27.6
0.5(1)
0
27.6
0.5(1)
0
;
27.6
27.6
FC501