Indication Messages; Internal Faults; Warnings - ABB REG650 Commissioning Manual

Relion 650 series generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 049-UEN A
8.2
8.2.1
8.2.2
Commissioning manual

Indication messages

Internal faults

When the Ready LED indicates an internal fault by flashing, the message associated
with the fault is found in the internal event list in the LHMI menu Main menu/
Diagnostics/Internal events. The message includes the date, time, description and
signal state for the fault. The internal event list is not updated dynamically. The list is
updated by leaving the Internal events menu and then selecting it again. The current
status of the internal fault signals can also be checked via the LHMI in Main menu/
Diagnostics/IED status.
Different actions are taken depending on the severity of the fault. If the fault is found
to be permanent, the IED stays in internal fault mode. The IED continues to perform
internal tests during the fault situation.
When a fault appears, the fault indication message is to be recorded and stated when
requesting support or service.
Table 5:
Internal fault indications
Fault indication
Internal Fault
Real Time Clock Error
Internal Fault
Runtime Exec. Error
Internal Fault
SW Watchdog Error
Internal Fault
Runtime App Error
Internal Fault
File System Error
Internal Fault
TRM-Error
Internal Fault
COM-Error
Internal Fault
PSM-Error

Warnings

The warning message associated with the fault is found in the internal event list in the
LHMI menu Main menu/Diagnostics/Internal events. The message includes the
date, time, description and signal state for the fault. The current status of the internal
Section 8
Troubleshooting
Additional information
Hardware error with the real time clock.
One or more of the application threads
are not working properly.
This signal will be activated when the
terminal has been under too heavy load
for at least 5 minutes.
One or more of the application threads
are not in an expected state.
A file system error has occurred.
A TRM card error has occurred. The
instance number is displayed at the end
of the fault indication.
A COM card error has occurred. The
instance number is displayed at the end
of the fault indication.
A PSM card error has occurred. The
instance number is displayed at the end
of the fault indication.
121

Advertisement

Table of Contents
loading

Table of Contents