Testing The Synchrocheck Check - ABB REG650 Commissioning Manual

Relion 650 series generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 049-UEN A
6.9.1.2
Commissioning manual
3.1. U-Bus = 80% GblBaseSelBus and f-Bus = 50.25 Hz, to verify that the
function does not operate when frequency difference is above limit.
4.
Repeat with different frequency differences for example, 100 mHz with f-Bus
nominal and line leading and for example 20 mHz (or just above FreqDiffMin)
to verify that independent of frequency difference the closing pulse occurs
within 2 degrees.
5.
Verify that the closing command is not issued when the frequency difference is
less than the set value FreqDiffMin.

Testing the synchrocheck check

During the test of SESRSYN for a single bay arrangement, these voltage inputs are
used:
U-Line
UL1, UL2 or UL3 line 1 voltage inputs on the IED
U-Bus
Bus voltage input on the IED
Testing the voltage selection for single 1 1/2 CB arrangements
At test of the SESRSYN function for a 1½ CB diameter the following alternative
voltage inputs can be used for the three SESRSYN (SESRSYN 1, SESRSYN 2,
SESRSYN 3) functions. These three SESRSYN functions can either be in one, two or
three different IEDs. Table
and SESRSYN 3 all are in the same IED. If SESRSYN 3 is in another IED, Bus1 will
be considered as Bus2 and Line2 as Line1. The voltage is selected by activation of
different inputs in the voltage selection logic as shown in table
Table 4:
Voltage selection logic
SESRSYN
CBConfig
setting
SESRSYN 1
1 ½ bus
(Operates on
CB
CB1QA1)
SESRSYN 2
Tie CB
(Operates on
CB2QA1)
Table continues on next page
4
describes the scenario when SESRSYN 1, SESRSYN 2
Section to
Activated
Activated
be
B1QCLD
B2QCLD
synchroniz
input on
input on
ed
IED from
IED from
Bus1 –
Line1
Bus1 –
CB2QA1
Line2
Bus1 –
CB2QA1
CB3QA1
Bus2
Line1 –
Line2
Bus1 –
CB1QA1
Line2
Bus2 –
CB3QA1
Line1
Bus1 –
CB1QA1
CB3QA1
Bus2
Section 6
Testing functionality
4
and figure 21.
Activated
Activated
Indication
LN1QCLD
LN2QCLD
from
input on
input on
SESRSYN
IED from
IED from
on IED
LN1QB9
B1SEL,
LN1SEL
LN2QB9
B1SEL,
LN2SEL
B1SEL,
B2SEL
LN1QB9
LN2QB9
LN1SEL,
LN2SEL
LN2QB9
B1SEL,
LN2SEL
LN1QB9
B2SEL,
LN1SEL
B1SEL,
B2SEL
101

Advertisement

Table of Contents
loading

Table of Contents