ABB REG650 Commissioning Manual page 73

Relion 650 series generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 049-UEN A
Commissioning manual
=
×
Tinv
kSN Sref
/ 3
IECEQUATION2403 V1 EN
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Continue to test another function or complete the test by setting the test mode to
Off.
Operation mode 3I
0
1.
Set the polarizing voltage to 1.2 · UNRel> and the phase angle between voltage
and current to the set characteristic angle (RCADir), the current lagging the
voltage.
2.
Measure that the operate power is equal to the INDir> setting for the set
directional element.
Note that for operation, both the injected current and voltage
must be greater than the set values INRel> and UNRel>
respectively.
The function activates the START and STDIRIN output.
Measure with angles j around RCADir +/- ROADir.
3.
4.
Compare the result with the set values, refer to figure
characteristic.
5.
Measure the operate time of the timer by injecting a current to get two times the
set SN_> operate value.
=
×
Tinv
kSN Sref
/ 3
IECEQUATION2403 V1 EN
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Continue to test another function or complete the test by setting the test mode to
Off.
( )
j
×
×
I
3
U
cos
0
test
0
test
and φ
( )
j
×
×
I
3
U
cos
0
test
0
test
Section 6
Testing functionality
(Equation 12)
17
for example
(Equation 13)
65