ABB REG650 Commissioning Manual page 110

Relion 650 series generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 6
Testing functionality
102
SESRSYN
CBConfig
setting
SESRSYN 3
1 ½ bus
(Operates on
alt. CB
CB3QA1)
(mirrored)
CB1QA1
(SESRSYN 1)
LN1QB9
Line 1
IEC11000274 V2 EN
Figure 21:
Objects used in the voltage selection logic
Testing the voltage difference
Set the voltage difference to 0.15 p.u. on the local HMI, and the test should check that
operation is achieved when the voltage difference UDiffSC is lower than 0.15 p.u.
The settings used in the test shall be final settings. The test shall be adapted to site
setting values instead of values in the example below.
Test with no voltage difference between the inputs.
Test with a voltage difference higher than the set UDiffSC.
Section to
Activated
Activated
be
B1QCLD
B2QCLD
synchroniz
input on
input on
ed
IED from
IED from
Bus2 –
Line2
Bus2 –
CB2QA1
Line1
Bus2 –
CB2QA1
CB1QA1
Bus1
(SESRSYN 3)
CB2QA1
(SESRSYN 2)
LN2QB9
Line 2
IEC11000274-2-en.vsd
1MRK 502 049-UEN A
Activated
Activated
LN1QCLD
LN2QCLD
input on
input on
IED from
IED from
LN2QB9
LN1QB9
Bus 1
Bus 2
CB3QA1
Commissioning manual
Indication
from
SESRSYN
on IED
B2SEL,
LN2SEL
B2SEL,
LN1SEL
B1SEL,
B2SEL