Load encroachment LEPDIS

Prepare the IED for verification of settings as outlined in
verify
settings".
Values of the logical signals for LEPDIS are available on the local HMI under Main
menu/Tests/Function status/Impedance/LEPDIS/LEPDIS:1. The Signal
Monitoring in PCM600 shows the same signals that are available on the local HMI.
Load encroachment operates on the same measuring principles as the impedance
measuring zones. Thus, it is necessary to follow the same principles as for distance
protection when performing the secondary injection tests.
Measure operating characteristics during constant current conditions. Keep the
measured current as close as possible to the rated value of its associated input
transformer or lower. Ensure, however, that it is higher than 30% of the rated current.
COMMON TRIP COMMAND (trip)
TRIPZ1 (tripZone1)
TRIPZ2 (tripZone2)
START (start)
GENMODE (generatorMode)
MOTMODE (motorMode)
1
1.5
2
2.5
time in seconds