ABB REG650 Commissioning Manual page 72

Relion 650 series generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 6
Testing functionality
64
Instrument
transformer
angle error
IEC06000651 V2 EN
Figure 16:
Explanation of RCAcomp
Operation mode 3I
0
1.
Set the polarizing voltage to 1.2 · UNRel> and the phase angle between voltage
and current to the set characteristic angle (RCADir), the current lagging the
voltage.
2.
Measure that the operate power is equal to the SN> setting for the set directional
element.
Note that for operation, both the injected current and voltage must be greater
than the set values INRel> and UNRel> respectively.
The function activates the START and STDIRIN outputs.
Measure with angles j = RCADir +/- 45° that the measuring element operates
3.
· cos (RCADir - j) = 3I0 · 3U0 · cos(+/-45) = SN>.
when 3I
· 3U
0
0
4.
Compare the result with the set value. Take the set characteristic into
consideration, see figure
5.
Measure the operate time of the timer by injecting 1.2 · UNRel> and a current to
get two times the set SN> operate value.
a
RCAcomp
3I
(to prot)
3I
(prim)
0
0
· 3U
· cosφ
0
15
and figure 16.
1MRK 502 049-UEN A
RCADir = 0º
Operate area
-3U
=U
0
ref
Characteristic after
angle compensation
en06000651.vsd
Commissioning manual