Pid Mini-Wizard - Eaton H-Max Series Quick Start Manual

Hvac drives
Hide thumbs Also See for H-Max Series:
Table of Contents

Advertisement

Eaton H-Max—Startup

PID Mini-Wizard

The PID Mini-Wizard is activated in the Quick Setup menu.
This Wizard presupposes that you are going to use the PID
controller in the "one feedback/one setpoint" mode. The
control place will be I/O A and the default process unit "%".
The PID Mini-Wizard asks for the following values to be set:
1
FeedBack1 Srce
2
Process Unit Selection
3
Process Unit Min
4
Process Unit Max
5
P-Gain
6
Integration Time
7
SetPT1 Source
8
H-Max HVAC Drives MN04008004E—September 2011 www.eaton.com
AI2
AI1
Not Used
ProceDataIn8
ProceDataIn7
ProceDataIn6
ProceDataIn5
ProceDataIn4
ProceDataIn3
ProceDataIn2
ProceDataIn1
AI6
AI5
AI4
AI3
(Several Selections)
Min: 0%
Max: 200%
Min: 0.00s
Max: 600.00s
Keypad SP1
Not Used
ProceDataIn8
ProceDataIn7
ProceDataIn6
ProceDataIn5
ProceDataIn4
ProceDataIn3
ProceDataIn2
ProceDataIn1
AI6
AI5
AI4
AI3
AI2
AI1
Multi-Pump
If Multi-Pump is the selected application, parameter group
2.16 will be visible in the menu structure. Default values may
need to be adjusted to meet your application needs.
Parameter
Parameter
Group Name
Number
Parameter Group 2.16:
P2.16.1
Multi-Pump
P2.16.2
P2.16.3
P2.16.4
P2.16.5
P2.16.6
P2.16.7
P2.16.8
P2.16.9
Parameter
Name
Number of motors
Interlock function
Include FC
Autochange
Autochange interval
Autochange frequency limit
Autochange motor limit
Bandwidth
Bandwidth delay

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents