Short Circuits
A SHORT condition reported by the RASTER indicates an
unintended re-routing of current flow somewhere between the
controller and the valve.
Short circuits can be caused by:
Shorted valve solenoids
•
Nicked or skinned field wires
•
Troubleshooting Opens and Shorts
To troubleshoot a valve station identified as OPEN or
SHORT:
Make sure the valves station wires are securely connected
to the controllers terminal strip.
If the wires are securely connected, move the stations wires
to a station that passed the RASTER. Then re-start the test.
44
Loose or corroded wire connections on the controllers
•
terminal strip or at the valve solenoid
Malfunctioning components on the controllers internal
•
circuit board
If the OPEN or SHORT recurs on the original station,
the controllers internal circuitry may need service.
If the OPEN or SHORT moves to the new station, check
the valves solenoid and field wiring.