Unit name
Transistor Output Unit
Number of points
2 points
I/O refreshing method
Output refreshing with specified time stamp
Indicators
TS indicator, output indicator
Dimensions
12 (W) x 100 (H) x 71 (D)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
I/O power supply
Supply from the NX bus
method
NX Unit power con-
• Connected to a CPU Unit
sumption
0.85 W max.
• Connected to a Communications Cou-
pler Unit
0.50 W max.
Weight
70 g max.
Circuit layout
NX bus
connector
(left)
Installation orienta-
Installation orientation:
tion and restrictions
• Connected to a CPU Unit
Possible in upright installation.
• Connected to a Communications Coupler Unit
Possible in 6 orientations.
Restrictions: No restrictions
A - 42
I/O power supply +
I/O power supply −
This Unit uses a push-pull output circuit.
Model
NX-OD2258
External connection
Screwless clamping terminal block (8 ter-
terminals
minals)
Internal I/O common
PNP
Rated voltage
24 VDC
Operating load voltage
15 to 28.8 VDC
range
Maximum value of load
0.5 A/point, 1 A/Unit
current
Maximum inrush cur-
4.0 A/point, 10 ms max.
rent
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON/OFF response time
300 ns max./300 ns max.
Isolation method
Digital isolator isolation
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Current capacity of I/O
IOV: 0.5 A/terminal max., IOG: 0.5 A/termi-
power supply terminal
nal max.
Current consumption
40 mA max.
from I/O power supply
NX-series Digital I/O Unit User's Manual (W521)
IOV0 to 1
OUT0 to OUT1
Terminal block
IOG0 to 1
I/O power supply +
NX bus
connector
I/O power supply −
(right)