5 I/O Refreshing
Network Configuration
The network configuration is as follows.
A Slave Terminal with the following configuration is connected at EtherCAT node address 1. The
device names that are given in the following table are used.
Unit number
0
NX-ECC201
1
NX-ID3344
2
NX-OD2154
Task Settings
The task period of the primary periodic task is 1 ms.
Unit Operation Settings
The Unit operation settings of the Input Unit NX-ID3344 are as follows.
Time Stamp (Trigger Setting) : Input
Bit 00 Trigger Setting
Time Stamp (mode Setting) : Input Bit
00 Mode Setting
5 - 34
Model
EtherCAT Coupler Unit
Digital Input Unit that supports input refreshing
with input changed time
Digital Output Unit that supports output refreshing
with specified time stamp
Set
Item
value
FALSE
FALSE
Unit
Meaning
Trigger to read the input changed time: Rising Edge
Operation mode to read the input changed time: Continuous
(Last changed time)
NX-series Digital I/O Unit User's Manual (W521)
Device name
E001
N1
N2