6 Incremental Encoder Input Units
Setting with the Sysmac Studio
1
Double-click the Incremental Encoder Input Unit in the Multiview Explorer.
The following tab page is displayed.
2
Set the parameters.

6-9-10 Pulse Rate Measurement

You can measure the number of input pulses in the specified time window for each counter.
You can use this information to calculate the pulse frequency and rotation rate in the user program.
Parameter name
Time Window
Average Processing
Times
*1. Pulse rate measurement is disabled (0) by default.
*2. Average processing is disabled (0) by default.
The time window for pulse rate measurement starts from the set value that is written and it starts when
the set value is written.
6 - 64
Setting
0 to 65,535 (ms)
*1
0
The setting unit is milli-
seconds.
0 to 100 times
*2
0
Default
You can change the value of this parameter
at any time.