Control and status area
68
This IR word contains information about the PROFIBUS-DP error
IR n+3
status.
IR n+3 will indicate the error type and the station address of the
station that is in error. If more than one station is in error, it will
report on the first station that is detected to be in error. After
removing the cause of the error it will report on the next station
that was found in error. If the error is in the master itself, the
Station address will show the value FFh.
The following table lists the error types.
Station
address
number
any
≠FFh
FFh
Note
When the PROFIBUS hardware does not function properly (P-DP
H/W failure, IR n+2.06 bit is ON), the contents of this word is set
to 0.
IR n+4
Unit Number and Message Length
When IR n+2.13 is set (Reply in output mailbox), this IR word
contains the length of the message that can be retrieved with an
IORD instruction. Combined with the Unit number, this constitutes
the correct source information for the IORD instruction. Refer to
section 6-3 for more details about the IORD instruction.
Note
When the PROFIBUS hardware does not function properly (P-DP
H/W failure, IR n+2.06 bit is ON), the contents of this word is set
to 0.
Error
Cause
00h
No errors
03h
Function in slave is
not activated
11h
No response of the
slave
12h
The Master is not
into the logical
token ring
36h
Error in
configuration data
38h
D4h
BE
Bus errors detected
other
Unit fault
Section 5-3
Action
Check if the slave is
conform
PROFIBUS-DP
norm and that the correct
GSD files are used
Check the bus cable and
the station address of the
remote node
Check the node address
of the master and the
highest station address of
other master systems.
Check if the cables are
connected properly.
Download the
configuration again
Check the bus
connections and cabling.
Try
downloading
the
configuration again; if the
same
error
occurs,
replace the Unit