Control and status area
15 14 13 12 11 10 9
IR n+3
15 14 13 12 11 10 9
IR n+4
IR n+2.00 Input data transferred
0: No input data has been transferred to the mapped PLC data
1: Input data has been transferred to the mapped PLC data
IR n+2.01 Not used by C200HW-PRM21.
IR n+2.02 Auto_clear (PROFIBUS-DP status bit).
0: Not in Auto_clear mode. This bit is also cleared during a
1: The master branched into Auto_clear mode, because of a
IR n+2.03 No_data (PROFIBUS-DP status bit).
0: All remote nodes are in data exchange mode. This bit is also
1: At least one remote node is not in the data exchange mode or
8
7
6
5
4
8
7
6
5
4
area(s) during the last I/O refresh.
area(s) during the last I/O refresh.
The Unit does not always transfer input data to the mapped
PLC data area(s). If the Unit cannot provide updated input
data during an I/O refresh, no data will be transferred. This will
typically occur if the fieldbus cycle time is larger than the PLC
cycle time, or if the DP communication has been inhibited.
database download or a P-DP H/W failure is detected (IR
n+2.06 is set).
remote node error.
The master will only branch into Auto_clear mode when this
has been enabled in the configuration (see 4-3-7, Bus
parameters). In Auto_clear mode, the network state bits
indicate Stop, and the DP-ERR LED is flashing. IR n+3 will
indicate more details about the cause of the error.
To recover from Auto_clear mode, the C200HW-PRM21 must
be restarted (Power OFF / ON or restart bit in AR01 / SR281).
cleared during a database download or when a P-DP H/W
failure is detected (IR n+2.06 is set).
reports a fatal error.
The DP-ERR LED is FLASHING to indicate this error. IR n+3
contains more details about the cause.
3
2
1
0
3
2
1
0
Message length (001~128)
Unit number (0 ~ F)
Section 5-3
Error number
Station address
65