Setting - Mitsubishi Electric FX2N-485-BD User Manual

Fx2n series melsec-f programmable controllers communication board
Hide thumbs Also See for FX2N-485-BD:
Table of Contents

Advertisement

FX
-485-BD COMMUNICATION BOARD
2N
7
7.3

Setting

Each setting for the N:N network becomes valid when the program is run or when the power of the programmable controller
is turned on.
7.3.1
Setting the Station No. (D8176)
Set a value 0 to 7 to the special data register D8176.
Set value
0
Master station
Salve station No.
1 to 7
Example : 1 is Slave station No. 1, 2 is Slave station No. 2
7.3.2
Setting the Total Number of Slave Stations (D8177)
Set a value 1 to 7 to the special data register D8177. (Default = 7)
This setting is not required for the slave station.
Decryption
Set value
1
2
:
7
N:N NETWORK
Description
1 slave station
2 slave station
:
7 slave station
7-4