Failure
VEGAPULS 63 • 4 ... 20 mA/HART two-wire
The following table shows the error codes in the status message
"Failure" and gives information on the reason and rectification. Keep
in mind that some information is only valid with four-wire instruments.
Code
Cause
Text mes-
sage
F013
– Sensor does not detect an
echo during operation
no measured
– Antenna system contami-
value avail-
nated or defective
able
F017
– Adjustment not within
specification
Adjustment
span too small
F025
– Index markers are not con-
tinuously rising, for examle
Error in the
unlogical value pairs
linearization
table
F036
– Failed or interrupted soft-
ware update
No operable
software
F040
– Hardware defect
Error in the
electronics
F080
– General software error
F105
– The instrument is still in the
start phase, the measured
Determine
value could not yet be
measured
determined
value
F113
– EMC interferences
– Transmission error with the
Communica-
external communication
tion error
with 4-wire power supply
unit
F125
– Temperature of the elec-
tronics in the non-specified
Unpermissi-
section
ble electronics
temperature
F260
– Error in the calibration car-
ried out in the factory
Error in the
– Error in the EEPROM
calibration
F261
– Error during setup
– False signal suppression
Error in the
faulty
configuration
– Error when carrying out a
reset
9 Diagnosis, Asset Management and service
Rectification
– Check or correct installation
and/or parameter adjust-
ment
– Clean or exchange process
component or antenna
– Change adjustment accord-
ing to the limit values (dif-
ference between min. and
max. ≥ 10 mm)
– Check linearization table
– Delete table/Create new
– Repeat software update
– Check electronics version
– Exchanging the electronics
– Send instrument for repair
– Exchanging the electronics
– Send instrument for repair
– Separate operating voltage
briefly
– Wait for the warm-up phase
– Duration depending on
the version and parameter
adjustment up to approxi-
mately 3 min.
– Remove EMC influences
– Exchange 4-wire power
supply unit or electronics
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
– Exchanging the electronics
– Send instrument for repair
– Repeat setup
– Repeat reset
51