Vega VEGAPULS 63 Operating Instructions Manual page 17

Radar sensor for continuous level measurement of liquids, 4...20 ma/hart two-wire
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Sensor orientation
Vessel installations
Agitators
VEGAPULS 63 • 4 ... 20 mA/HART two-wire
d
Fig. 10: Deviating socket dimensions
Align the sensor in liquids as vertical as possible to the product sur-
face to achieve an optimum measurement.
Fig. 11: Alignment in liquids
The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-
rals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring site that the radar sensor
has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be
carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.
Fig. 12: Cover smooth profiles with deflectors
If there are agitators in the vessel, a false signal memory should be
carried out with the agitators in motion. This ensures that the interfer-
4 Mounting
d
h
max.
50 mm/2"
100 mm
80 mm/3"
150 mm
100 mm/4"
250 mm
150 mm/6"
400 mm
17