Electrical Characteristics; Table 10 Liebert Exm Bdc Input Currents, Single Input, Main, Without Transformer; Table 11 Liebert Exm Bdc Input Currents, Dual Input, Rectifier, Without Transformer - Liebert EXM BDC User Manual

10-100kva, 60hz
Table of Contents

Advertisement

3.1

Electrical Characteristics

NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be
provided for AC input, Bypass and AC output. Recommended cable sizes are suitable for operation at a
maximum temperature of 104°F (40°C).
Table 10
Liebert EXM BDC input currents, single input, main, without transformer
Voltage
BDC Rating
System Input
3-Ph, 60 Hz
kVA
Current, A, Max
208/120
10
220/127
208/120
15
220/127
208/120
20
220/127
208/120
30
220/127
208/120
40
220/127
208/120
60
220/127
208/120
80
220/127
208/120
100
220/127
Table 11
Liebert EXM BDC input currents, dual input, rectifier, without transformer
Voltage
BDC Rating,
3-Phase, 60Hz
kVA
Current RIB, A, Max
208/120
10
220/127
208/120
15
220/127
208/120
20
220/127
208/120
30
220/127
208/120
40
220/127
208/120
60
220/127
208/120
80
220/127
208/120
100
220/127
Refer to Figures 26 and27 for additional details about this system configuration.
Vertiv
| Liebert
®
EXM
BDC User Manual | Rev. 3 | 01/18 |
Recommended
Phase
Protection, A
34
3W + N + G
51
3W + N + G
68
3W + N + G
102
3W + N + G
136
3W + N + G
205
3W + N + G
273
3W + N + G
341
3W + N + G
Rectifier
Recommended
Rectifier Input
Upstream
Protection, A
34
45
51
70
68
90
102
150
136
175
205
300
273
350
341
450
Upstream
75°C Wire
Current, A, Total Copper Wire
45
65
70
85
90
115
150
175
175
230
300
400
350
460
450
610
75°C Wire
Phase
Current, A, Total Copper Wire
3W + N + G
65
3W + N + G
85
3W + N + G
115
3W + N + G
175
3W + N + G
230
3W + N + G
400
3W + N + G
460
3W + N + G
610
Aluminum
Wire
Bolt Size
(1) #6
(1) #4
M12
(1) #4
(1) #2
M12
(1) #2
(1) 1/0
M12
(1) 2/0
(1) 4/0
M12
(1) 4/0
(2) 1/0
M12
(2) 3/0
(2) 4/0
M12
(2) 4/0
(2) 300kcmil
M12
(2) 350kcmil (2) 400kcmil
M12
Aluminum
Wire
Bolt Size
(1) #6
(1) #4
M12
(1) #3
(1) #2
M12
(1) #2
(1) 1/0
M12
(1) 2/0
(1) 4/0
M12
(1) 4/0
(2) 1/0
M12
(2) 3/0
(2) 4/0
M12
(2) 4/0
(2) 300kcmil
M12
(2) 350kcmil (2) 400kcmil
M12
36

Advertisement

Table of Contents
loading

Table of Contents