Table 3
Output dry contact relays
Port
Pin
Name
1
MFP_O
J24
3
MFP_S
5
MFP_C
2
INV_O
J23
4
INV_S
6
INV_C
1
BFP_O
J23
3
BFP_S
5
BFP_C
2
MAIN_O
J24
4
MAIN_S
6
MAIN_C
Vertiv
| Liebert
®
™
EXM
BDC User Manual | Rev. 3 | 01/18 |
Description
Rectifier back-feed normally open contact. Open when there is no back-feed.
Rectifier back-feed common contact.
Rectifier back-feed normally closed contact. Closed when there is no back-feed.
Inverter state normally open contact. Open when the inverter is abnormal.
Inverter state common contact.
Inverter state normally open contact. Closed when the inverter is normal.
Bypass back-feed normally open contact. Open when there is no back-feed.
Bypass back-feed common contact.
Bypass back-feed normally closed contact. Closed when there is no back-feed.
Rectifier input state normally open contact. Open when the rectifier is abnormal.
Rectifier input state common contact.
Rectifier input state normally closed contact. Closed when the rectifier is normal.
19