Figure 15 Liebert Exm Bdc With Two Subfeed Breakers-Main Components - Liebert EXM BDC User Manual

10-100kva, 60hz
Table of Contents

Advertisement

Figure 15
Liebert EXM BDC with two subfeed breakers—Main components
BOTTOM
LEFT SIDE
Panel Removed
Vertiv
| Liebert
®
EXM
BDC User Manual | Rev. 3 | 01/18 |
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Copper cables only are recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. When the Liebert EXM BDC is attached to the UPS,
Vertiv will supply the interconnection cables.
6. 225A panelboard for 10k-40kVA only. 400A panelboard for 60-100kVA only
TOP
23.6" (600mm)
Neutral
Busbar
MBB
BIB
System
Input
Bus
Ground
Busbar
FRONT
Door Removed
37.5" (953mm)
Subfeed
Breakers
MIB
Neutral
Bus
RIGHT SIDE
Panel Removed
LDMF
inside front
door
EXM16013
Rev. 0
21