Electrical Characteristics (Input Rectifier); Electrical Characteristics (Intermediate Dc Circuit) - Liebert APM 150 User Manual

Integrated ups single module and parallel system
Table of Contents

Advertisement

11.4 Electrical Characteristics (Input Rectifier)

Item
Rated AC input voltage
Input voltage tolerance
Frequency
2
Power factor
Input power
Input current
Total current harmonic
distortion (THD)
Duration of progressive
power walk-in
1. Rectifiers operate at any of the rated supply voltages and frequencies without further adjustment.
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously
charged battery.
3. IEC62040-3/EN50091-3: at rated load and input voltage 400V, battery fully charged.
4. IEC62040-3/EN50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.

11.5 Electrical Characteristics (Intermediate DC Circuit)

Item
Battery bus voltage
Number of
lead-acid cells
Float voltage
Temperature
compensation
Ripple voltage
Ripple current
Boost voltage
Boost control
EOD voltage
Liebert APM 150 Integrated UPS Single Module And Parallel System
Table 11-4 Rectifier AC input (mains)
Unit
Vac
1
Vac
2
Hz
kW/kVA, full load (half
load)
kVA rated
(maximum
3
A rated
3
(maximum
4
)
%
s
Table 11-5 Battery
Unit
30
Nominal: 432V (VRLA float charge is 540V), range: 300V ~ 576V
Vdc
Nominal
36 = [a cell (12V)]
Maximum
40 = [a cell (12V)]
Minimum
30 = [a cell (12V)]
2.25V/cell (selectable from 2.2V/cell to 2.3V/cell)
V/cell (VRLA)
Constant current and constant voltage charge mode
mV/°C/cl
-3.0 (selectable from 0 to -5.0 around 25°C or 30°C, or inhibit)
≤1
% V float
≤5
% C
10
2.35V/cell (selectable from 2.30V/cell to 2.40V/cell)
VRLA
Constant current and constant voltage charge mode
Float-boost current trigger 0.050C
Boost-float current trigger 0.010C
24hr safety time timeout (selectable from 8hr to 30hr)
Boost mode inhibit also selectable
1.63V/cell (selectable from 1.60V/cell to 1.750V/cell)
Automatic inverse EOD voltage × discharge current mode
V/cell (VRLA)
(the EOD voltage increases at low discharge currents)
380/400/415 (3-phase and sharing neutral with the bypass
input)
305 ~ 477; 304 ~ 228 (output derated below 80%)
50/60 (tolerance: 40Hz ~ 70Hz)
0.99 (0.98)
30 ~ 120
)
4
60 ~ 240
≤3
10s to reach full rated current (selectable 5s through 30s in
5-second intervals)
Rated power (kVA)
60
90
10
(selectable from 0.005 to 0.025)
10
Chapter 11 Specifications
Rated power (kVA)
30 ~ 120
120 (with redundant
120
power module)
(selectable from 0.030 to 0.070)
User Manual
81