Figure 19
Lineup arrangement, Liebert EXM with Liebert EXM BDC
47.6" (1208mm)
23.6"
23.6"
(600mm)
(600mm)
UPS
BDC
FRONT VIEW
Vertiv
| Liebert
®
EXM
BDC User Manual | Rev. 3 | 01/18 |
NOTES
1. Dimensions are in inches (mm).
2. 24" (610mm) minimum clearance above unit.
36" (914mm) front access required for service.
For seismic mounting only 5" (102mm) in rear
for mounting brackets
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates.
78.7"
Remove, punch to suit conduit size and replace.
(2000mm)
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. All wiring is to be in accordance with national and
local electrical codes.
8. Bypass distribution cabinet must be positioned on the right
side of the UPS.
EXM13028
Rev. 2
25