Table 20
Electrical data—Liebert EXM BDC, 208VAC or 220VAC input, single input, with 208V:208V or 220V:220V
transformer
Liebert EXM
Maximum System
BDC Rating, kVA
Input Current, A
40
141
60
211
80
281
100
352
See Notes on Tables 18 through20. below.
Notes on Tables 18 through20.
1.
Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input
current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are
defined in NEC 100. Recommended overcurrent protection is based on 80% rated devices.
*The recommended overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215.
2.
Maximum input current is controlled by the current limit setting.
3.
Recommended AC input external overcurrent protection is based on 80% rated devices and maximum input current limit
setting.
4.
Recommended AC output external overcurrent protection is based on 80% rated devices and full rated output current.
5.
Nominal battery voltage is shown at 2 volts per cell.
6.
Input power factor of 0.99 is used for the calculations.
Vertiv
| Liebert
®
EXM
BDC User Manual | Rev. 3 | 01/18 |
Recommended
Upstream
Phase
Protection, A
Current, A, Total
3W + G
200
3W + G
300
3W + G
400
3W + G
450
75°C Wire
Copper Wire
230
(1) 4/0
335
(1) 400 kcmil
460
(2) 4/0
510
(2) 250 kcmil
Aluminum
Wire
Bolt Size
(1) 300 kcmil
M12
(2) 4/0
M12
(2) 300 kcmil
M12
(2) 400 kcmil
M12