Honeywell VisionPRO 8000 Product Data page 31

With wi-fi
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
904
Dehum Wiring
U1
905
Dehum Terminal -
Normally Closed
U1
Normally Open
907
Dehum Over
0°, 1°, 2°, 3° F
Cooling Limit
908
DehumControl
Basic
Minimum On Time
Cooling Droop
Reheat
909
Dehum Minimum
5 to 15 minutes
On Time
910
Dehum Over
1° F to 5° F
Cooling Limit
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Thermostat defaults
to the unused
universal terminal
U1.
Defaults to Normally
Closed when ISU
900 Dehum
Equipment is A/C
with Low Fan
Defaults to Normally
Open when ISU 900
Dehum Equipment is
Hot Gas Bypass
3° F
Basic
10 minutes
2° F
Residential,
Commercial
or Both
Both
U1 are dry contacts that require power. See
"Wiring IAQ Equipment or a Heat/Cool Stage to
the Universal Terminals" beginning on page 86.
Both
Choose an option appropriate for the type of
equipment installed.
Normally Open: U1 will normally be open and
will close when the thermostat calls for
dehumidification.
Normally Closed: U1 will normally be closed
and will open when the thermostat calls for
dehumidification.
Residential
This ISU is only displayed when ISU 900 Dehum
Equipment is set to A/C with Low Fan or A/C
with High Fan.
The thermostat uses the cooling system to
reduce humidity by lowering the temperature up
to 3° F below the current cool setpoint until the
desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
0° F is only an option when ISU 900 Dehum
Equipment is set to A/C with Low Fan.
Commercial
See "Dehumidification - Commercial" beginning
on page 64.
Commercial
This ISU is only displayed if ISU 908 Dehum
Control is set to Minimum On Time. This option
ensures that the compressor runs long enough
to effectively reduce humidity when the cooling
equipment is cycled on. The compressor will
run for the "minimum on time" you set until the
desired humidity level is reached.
Commercial
This ISU is only displayed if ISU 908 Dehum
Control is set to Cooling Droop. The thermostat
uses the cooling system to reduce humidity by
lowering the temperature up to 5° F below the
current cool setpoint until the desired humidity
level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
31
®
VISIONPRO
8000 WITH WI-FI
Notes
33-00096—01
®