Honeywell VisionPRO 8000 Product Data page 24

With wi-fi
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH WI-FI
ISU
Installer Setup
Number
Name
405
Min. Heat
Off
Recovery Outdoor
-20° F to 100°F
Temp
406
Max. Heat
Off
Recovery Ramp
1° F/hr to 20° F/hr
Rate
33-00096—01
®
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
0° F
8° F/hr
Residential,
Commercial
Default
or Both
Commercial
Commercial
24
Notes
Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a cold day in your region. Default setting is
5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day
in your region to be associated with the
Minimum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save energy
during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Off: The heating system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a mild day in your region. Default setting is
8° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to be
associated with the Maximum Recovery Ramp
Rate. The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature.