Honeywell VisionPRO 8000 Product Data page 21

With wi-fi
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
315
Heat Cycles Per
1 to 12 CPH
Hour Stage 3
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type.
316
Backup Heat
1 to 12 CPH
Cycles Per Hour
Stage 1
Note: "Stage 1" is
not displayed if
there is only 1
stage.
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Conv. Forced Air = 5
CPH
Heat Pump =
3 CPH
Radiant Heat = 3
CPH
Electric =
9 CPH
Gas / Oil =
5 CPH
Residential,
Commercial
or Both
Both
This ISU is only displayed when ISU 207 Heat
Stages is set to 3 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load. The recommended cycle rate settings
are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Both
This ISU is only displayed when ISU 207 or 213
Backup Heat Stages is set to 1 stage.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load. The recommended cycle rate settings
are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
21
®
VISIONPRO
8000 WITH WI-FI
Notes
33-00096—01
®