VISIONPRO
8000 WITH WI-FI
ISU
Installer Setup
Number
Name
303
Cool Differential
Comfort
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
303
Cool Differential
Comfort
Stage 3
1.0°F - 4.0°F from setpoint (in
0.5° F increments)
305
Heat Differential
Comfort
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type
33-00096—01
®
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Comfort
Comfort
Comfort
Residential,
Commercial
Default
or Both
Both
Commercial
Both
16
Notes
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat
is set to 2 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 2 turns on. When
set to Comfort, the thermostat uses the stage of
cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the thermostat
is set to 3 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 3 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 3 turns on. When
set to Comfort, the thermostat uses the stage of
cooling as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed for conventional
systems that have 2 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C) away
from the setpoint before stage 2 turns on. When
set to Comfort, the thermostat will use the stage
of heating as needed to keep the indoor
temperature within 1° F (0.5° C) degree of the
setpoint.