Honeywell VisionPRO 8000 Product Data page 19

With wi-fi
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
313
Radiant Cycles
1 to 12 CPH
Per Hour Stage 1
Note: "Stage 1" is
not displayed if
there is only 1
stage of Radiant
Heat.
314
Cool /
1 to 6 CPH
Compressor
Cycles Per Hour
Stage 1
Note: "Stage 1" is
not displayed if
there is only 1
stage.
314
Cool /
1 to 6 CPH
Compressor
Cycles Per Hour
Stage 2
314
Cool Cycles Per
1 to 6 CPH
Hour Stage 3
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
3
3
3
3
Residential,
Commercial
or Both
Both
This ISU is only displayed when ISU 201
Heating Equipment is Geothermal Radiant.
The thermostat automatically defaults to the
recommended setting for Geothermal Radiant
Heat (3 CPH).
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
Both
This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
Both
This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
Commercial
This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207
Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period
measured at a 50% load. For example, when set
to 3 CPH, at a 50% load, the most the system
will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when
load conditions are less than or greater than a
50% load.
19
®
VISIONPRO
8000 WITH WI-FI