Honeywell VisionPRO 8000 Product Data page 28

With wi-fi
Hide thumbs Also See for VisionPRO 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH WI-FI
ISU
Installer Setup
Number
Name
501
Indoor Sensor
[Select Indoor Sensor Name]
Name
502
Indoor Sensor
S1
503
Indoor Sensor
10K
Type
20K
504
Use [T-Stat Sensor]
Use T-Stat Sensor for Temp Ctrl -
for Temp Ctrl
Yes or No
505
Outdoor Sensor
S1
509
Discharge Sensor
S1
510
Discharge Sensor
10K
Type
20K
511
A-Coil Low Temp.
Off
Cutoff
35° F to 65° F (in 5° F
increments)
700
Filter Type
None
Elec. Air Cleaner
Media
702
Number of Air
1 to 2
Filters
711
Air Filter 1
Off
Reminder
Run Time:
Note: "1" is not
10, 20, 30, 45, 60, 90, 120, 150
displayed if there
days
is only 1 filter.
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
33-00096—01
®
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Indoor Sensor
10K:
if ISU 101
Application is
Residential
20K:
if ISU 101:
Application is
Commercial
Sensors are
Averaged (T-Stat
Sensor and Remote)
10K
Off
Media
1
Off
Residential,
Commercial
Default
or Both
Both
Both
Both
Both
Both
Both
Both
Both
Both
Both
Both
28
Notes
Select a name (location) of the Wired Remote
Indoor Sensor.
Confirms type of sensor wired to S1.
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A
must be used in combination with a TR21
sensor or another TR21-A sensor for the
thermostat to calculate the correct indoor
temperature reading).
See "Wiring guide — Wired Indoor Sensors"
beginning on page 88 for information on the
sensor type you should select based on how the
sensors are wired. For example, you would
select 20K when you have two TR21-A (10K)
sensors wired in series.
Only displayed when a wired indoor sensor is
configured. Select Yes if you want the
thermostat to average with wired indoor sensor.
Select No if you want to sense temperature only
at the wired sensor.
Confirms type of sensor wired to S1.
Confirms type of sensor wired to S1.
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system fan
continues to run, until the temperature rises to a
safe level.