Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
measured value data record 143:
Error code in STATUS parameter
(hexadecimal)
Byte 0
Byte 1
Byte 2
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Manual, 10/2017, A5E36061895-AB
Meaning
Byte 3
00
Number of the data record unknown
00
Length of the data record incorrect
00
Slot invalid or cannot be accessed.
01
Reserved bits are not 0.
39
Incorrect version entered.
3A
Incorrect data record length entered.
3C
At least one start value is invalid.
3D
At least one start value is too large
7.5 Data record for energy counter (DS 143)
Solution
Enter a valid number for the data
record.
Enter a valid value for the data record
length.
Check the station whether the modu-
le is plugged or drawn.
Check the assigned values for the
parameters of the WRREC instruction
Check Byte 2...7 and set the reserved
bits back to 0.
Check Byte 0. Enter a valid version.
Check the parameters of the WRREC
instruction. Enter a valid length.
Check Bytes 8...103 and Bytes
158...169. The start values may not
be negative.
Check Bytes 8...103 and Bytes
158...169. Observe the ranges of
values for start values.
Energy counters
51