Article number
Measuring inputs for voltage
–
Measurable line voltage between phase
and neutral conductor
–
Measurable line voltage between the
line conductors
–
Measurable line voltage between phase
and neutral conductor, min.
–
Measurable line voltage between phase
and neutral conductor, max.
–
Measurable line voltage between the
line conductors, min.
–
Measurable line voltage between the
line conductors, max.
–
Measurement category for voltage
measurement in accordance with IEC
61010-2-030
–
Internal resistance line conductor and
neutral conductor
–
Power consumption per phase
–
Impulse voltage resistance 1,2/50µs
Measuring inputs for current
–
measurable relative current (AC), min.
–
measurable relative current (AC), max.
–
Continuous current with AC, maximum
permissible
–
Apparent power consumption per pha-
se for measuring range 5 A
–
Rated value short-time withstand cur-
rent restricted to 1 s
–
Input resistance measuring range 0 to 5
A
–
Zero point suppression
–
Surge strength
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Manual, 10/2017, A5E36061895-AB
6ES7134-6PA01-0BD0
230 V
400 V
90 V
264 V
155 V
460 V
CAT II; CAT III in case of guaranteed protection
level of 1.5 kV
3.4 MΩ
20 mW
1 kV
5 %; Relative to the secondary rated current; 1 A,
5 A
100 %; Relative to the secondary rated current; 1
A, 5 A
5 A
0.6 V·A
100 A
25 mΩ; At the terminal
Parameterizable: 20 ... 250 mA, default 50 mA
10 A; for 1 minute
Technical specifications
10.1 Technical specifications
69