Siemens SIMATIC ET 200SP Manual page 107

Analog input module ai energy meter 400vac st 6es7134-6pa01-0bd0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Byte
Measured variable
16...23
Active energy outflow (initial value) L1
24...31
Reactive energy inflow (initial value) L1
32...39
Reactive energy outflow (initial value) L1
40...47
Apparent energy (initial value) L1
48...55
Active energy inflow (initial value) L2
56...63
Active energy outflow (initial value) L2
64...61
Reactive energy inflow (initial value) L2
72...79
Reactive energy outflow (initial value) L2
80...87
Apparent energy (initial value) L2
88...95
Active energy inflow (initial value) L3
96...103
Active energy outflow (initial value) L3
104...111
Reactive energy inflow (initial value) L3
112...119
Reactive energy outflow (initial value) L3
120...127
Apparent energy (initial value) L3
Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
measured value data record 143:
Error code in STATUS parameter
(hexadecimal)
Byte 0
Byte 1
Byte 2
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E1
DF
80
E1
DF
80
E1
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Manual, 10/2017, A5E36061895-AB
Meaning
Byte 3
00
Number of the data record unknown
00
Length of the data record incorrect
00
Slot invalid or cannot be accessed.
01
Reserved bits are not 0.
39
Incorrect version entered.
3A
Incorrect data record length entered.
Measured value data records
E.3 Structure for energy counters (DS 143)
Data
Unit
Value range
type
LREAL
Wh
LREAL
varh
LREAL
varh
LREAL
VAh
LREAL
Wh
LREAL
Wh
LREAL
varh
LREAL
varh
LREAL
VAh
LREAL
Wh
LREAL
Wh
LREAL
varh
LREAL
varh
LREAL
VAh
Solution
Enter a valid number for the data
record.
Enter a valid value for the data record
length.
Check the station whether the modu-
le is plugged or drawn.
Check the assigned values for the
parameters of the WRREC instruction
Check Byte 2...7 and set the reserved
bits back to 0.
Check Byte 0. Enter a valid version.
Check the parameters of the WRREC
instruction. Enter a valid length.
Mea-
sured
value
ID
61181
61182
61183
61184
61200
61201
61202
61203
61204
61220
61221
61222
61223
61224