Reactive power L1L2L3 (ID 252 or FC
Table D- 4
Reactive power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Reactive power L1
10 ... 11
Reactive power L2
12 ... 13
Reactive power L3
14 ... 15
Total reactive power L1L2L3
16 ... 19
Total reactive energy L1L2L3
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling reactive power L1
28
Scaling reactive power L2
29
Scaling reactive power L3
30
Scaling reactive power L1L2L3
31
Scaling total reactive energy L1L2L3
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Manual, 10/2017, A5E36061895-AB
D.1 User data variants with 32 bytes input data / 12 bytes output data
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Data
Unit
Value range
type
BYTE
-
252 (FC
BYTE
Bit
qq xx xx xx
string
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
INT
1 var
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 var
-27648 ... 27648
DINT
1 varh
-2147483647 to
+2147483647
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
0.01
0 ... 100
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
User data variants
Mea-
sured
value
ID
)
-
H
-
66007
66008
66009
66016
66017
66018
66035
226
66019
66020
66021
66037
-
-
-
-
-
-
-
-
95