Siemens SIMATIC ET 200SP Manual page 56

Analog input module ai energy meter 400vac st 6es7134-6pa01-0bd0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters
8.1 Parameters
Parameters
Diagnostics
underflow voltage
Diagnostics
low limit voltage
Diagnostics
overflow cumulative
values
Overcurrent tolerance
value [0.1 A]
Overcurrent tolerance
time [ms]
Low limit for current
measurement [mA]
Current transformer
primary current [A]
Current transformer
secondary current
Reverse current direc-
tion
56
Value range
Disable
Enable
Disable
Enable
Disable
Enable
10 ... 100 [0.1 A]
1 ... 60000 ms
20 ... 250 mA
1 ... 10000 A
1 A
5 A
Disable
Enable
Default setting
Reconfigurati-
on in RUN
Disable
Yes
Disable
Yes
Disable
Yes
100 [0.1 A]
Yes
40000 ms
Yes
50 mA
Yes
1 A
Yes
1 A
Yes
Disable
Yes
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Effective range with configuration
software, e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel/phase
Module
Channel/phase
-
(blocking is
preset)
Channel/phase
Module
Channel/phase
Module
Channel/phase
Module
Module
-
(Default set-
ting: 20 mA)
Channel/phase
Module
(Value range:
1...65535)
Channel/phase
Module
Channel/phase
Module
Manual, 10/2017, A5E36061895-AB