2.1

General Specifications

Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the Hardware Edition manual of the connected PLC.
Item
Ambient temperature
Dielectric withstand voltage
Insulation resistance
Pollution degree
2.2

Power Supply Specification

Item
Driving power supply
External power supply for
ASLINK communication
*1.
The 128ASL-M supplies the internal power supply of slave modules and the connection load power
supply of non-isolated slave modules from transmission signals.
The following expression shows the rough value of the transmission cable supply current (A):
Transmission cable supply current = Internal current consumption of slave modules + Maximum
On some slave modules with cables, the cross-sectional area of the integrated transmission cables
(DP, DN) is 0.75mm
sectional area of normal transmission cables (DP, DN) meets the following requirements.
For slave modules with integrated transmission cables (DP, DN), the length of the transmission cables
(DP, DN) is included in the total length.
-
Relationship between the total length of the AnyWireASLINK system, the cross-sectional area of
connection cables and transmission cable supply current
Cross-sectional area
of transmission
cables
1.25 mm
0.75 mm
-
Quick reference chart of total length (m) and transmission cable supply current (A) (1.25 mm
2
1.0
0.6
0.5
0.4
0
16
0 to 55 °C (32 to 131 °F) when operating and -25 to 75 °C (-13 to 167 °F) when stored
500 V AC for one minute
5 MΩ or more by 500 V DC Megger
2 or less
130 mA / 5 V DC
5 V DC power is supplied internally from the main unit.
Voltage: 21.6 to 27.6 V DC (24 V DC -10% to +15%), ripple voltage 0.5 Vp-p or lower
Rated voltage: 24 V DC
* Please use a UL Class 2 power supply.
Module current consumption: 0.1 A
Transmission cable supply current
2
or less. However, they can be used without any problem, provided that the cross-
Total length of 50 m or less
2
Up to 2 A
2
Up to 1.2 A
0
10
50 60
100
Total length (m)
Specification
Between PLC all terminals and ground terminal
Specification
*1
: Up to 2 A
current consumption of sensors and actuators connected to
non-isolated slave modules
Transmission cable supply current
Total length of 50 m to 100 m
Up to 1 A
Up to 0.6 A
170
200
2 Specification
2.1 General Specifications
Total length of 100 m to 200 m
Up to 0.5 A
Up to 0.3 A