ERROR (ERR) LED [ON/Flicker/OFF]

The table below describes details for the LED statuses.
LED Status
A watchdog timer error may have occurred,
ON
or the hardware of the PLC may be
damaged.
One of the following errors has occurred on
the PLC:
Flicker
Parameter error
Syntax error
Ladder error
OFF
No errors to stop the PLC have occurred.
9.4

Diagnostics by GX Works2

Some functions of GX Works2 are available to check the status of the 128ASL-M, status of slave modules
and others.
For details of GX Works2 operation, refer to the following manual.
PLC Status
1) Stop the PLC, and turn the power ON again.
-
-
-
-
-
2) Remove the PLC and supply the power to it from another power source.
-
-
3) If the ERROR (ERR) LED does not go out even after measures in 1) and
Perform PLC diagnosis and program check with the programming tool.
If the operations of the PLC are abnormal, perform PLC diagnosis and
program check with the programming tool.
An I/O error, parallel link/communication error, or operation error may have
occurred.
→ GX Works2 Version 1 Operating Manual (Intelligent Function Module)
Error corrective action
If the ERROR (ERR) LED goes out, a watchdog timer error may have
occurred. Adopt any of the following measures:
Review the program.
Set the maximum value (D8012) lower than the watchdog timer value.
Check that the input used for input interrupt or pulse catch is not being
abnormally turned ON and OFF in one scan.
Check that the frequency of the pulse (duty 50%) input to the high-
speed counter is not exceeding the specified range.
Add WDT instructions.
Add some WDT instructions to the program, and reset the watchdog
timer several times in one scan.
Change the watchdog timer value.
Change the watchdog timer setting (D8000) in the program so that the
setting is larger than the maximum value of the scan time (D8012).
If the ERROR (ERR) LED goes out, noise may have affected the PLC.
Adopt the following measures:
Check the ground wiring, and re-examine the wiring route and
installation location.
Fit a noise filter onto the power supply line.
2) are adopted, consult your local Mitsubishi Electric representative.
→ GX Works2 Version 1 Operating Manual (Common)