2) AnyWireASLINK parameters
These parameters are common to all slave modules connected to AnyWireASLINK, and the description
and storage areas are common to all models.
Name
Module ID
Status details
Sensing level
66
BFM No.
decimal
12288 + (n × 48)
Indicates the slave module ID.
(n: 0 to 127)
0000H to 007FH: ID of output slave modules
1st of 48 words
0200H to 027FH: ID of input slave modules or I/O combined slave modules
Indicates the status of the slave module.
The status 1) to 6) of the slave module are indicated depending on the ON or OFF of
each bit as below.
b15
1) Module power supply status (b0)
ON: Slave module voltage drop
12327 + (n × 48)
OFF: No fault
(n: 0 to 127)
2) Sensing level status (b1)
40th of 48 words
ON: Sensing level drop
OFF: No fault
3) I/O disconnection (ASLINKER) (b2)
ON: I/O disconnection
OFF: No fault
4) I/O short-circuit (ASLINKER) (b3)
ON: I/O short-circuit
OFF: No fault
5) I/O power supply voltage drop (isolated slave module) (b5)
ON: No ID setting
OFF: No fault
6) Not used (b4, b6 to 15)
12328+ (n × 48)
The analog value of the connected ON/OFF sensor is displayed from 0 to 100
(n: 0 to 127)
(decimal).
41th of 48 words
7.3 Details of buffer memory
Description
•••••••
b6
b5
6)
5)
7 Buffer Memory
b3
b2
b1
b0
4)
3)
2)
1)