Transmission cycle time
(Rough value)
3.6 ms
4.8 ms
6.0 ms
Caution on the transmission cycle time
• The transmission delay time is a value between one and two transmission cycle times due to the double
check (described later).
• To ensure the response, provide an input signal that is longer than two transmission cycle times.
Number of input
Number of output
point settings
point settings
64
64
48
64
32
64
24
64
16
64
8
64
0
64
80
0
80
8
80
16
80
24
80
32
80
48
48
80
32
80
24
80
16
80
8
80
0
80
96
0
96
8
96
16
96
24
96
32
32
96
24
96
16
96
8
96
0
96
112
0
112
8
112
16
16
112
8
112
0
112
128
0
0
128
2.4 Communication Specifications
Condition, remarks
When the larger one between the number of assigned
input points and the number of assigned output points
meets the following expression, the transmission cycle
time becomes the value shown on the left:
32 < Number of input or output points ≤ 64
When the larger one between the number of assigned
input points and the number of assigned output points
meets the following expression, the transmission cycle
time becomes the value shown on the left:
64 < Number of input or output points ≤ 96
When the larger one between the number of assigned
input points and the number of assigned output points
meets the following expression, the transmission cycle
time becomes the value shown on the left:
96 < Number of input or output points ≤ 128
2 Specification